• @b34k
    link
    28 hours ago

    The bidet outlet just needs to be on the load side of the GFI.

    • NotNotMike
      link
      fedilink
      47 hours ago

      That statement presumes knowledge of GFI that I did not have - load side means nothing to a layperson

      • @b34k
        link
        16 hours ago

        On the back of the GFI the ports will be labeled, line or load. Line goes to the breaker box, load goes to all outlets you need protected.

      • @[email protected]
        link
        fedilink
        English
        16 hours ago

        Load side here essentially means end of the chain. So Breaker ---- anything else ----- GFI - Bidet ----nothing else.

        When you put a GFI receptical on a line there are two ways, either in series or parallel, if you do it in series then everything down stream of that outlet is protected by GFI. One thing you dont want to happen is two GFI on the same line, so if you have GFI breakers in your box dont add a GFI outlet on one.

        Good luck, its easy enough to install because its the same as really any outlet, you just need to know where it is in the chain.