https://www.ntsb.gov/investigations/Pages/DCA24MM031.aspx

https://www.ntsb.gov/investigations/Documents/DCA24MM031_PreliminaryReport 3.pdf

Power outage is on page 9.

Summary of that section*:

Around 0125, the vessel Dali experienced a critical electrical failure about 0.6 miles from the Key Bridge. Two electrical breakers tripped, causing a blackout that disabled shipboard lighting, equipment, main engine cooling water pumps, and steering gear pumps. Although generators 3 and 4 continued to run, the main propulsion engine shut down due to the loss of power to necessary pumps, and the vessel lost steering capabilities.

At 0126, the voyage data recorder (VDR) resumed recording data, indicating the ship’s heading and course had slightly changed, and speed had decreased. The senior pilot, having taken control, ordered a 20° port rudder, and the emergency generator started, providing limited power for emergency equipment, including a slow-moving emergency steering pump.

The crew manually restored power by closing the tripped breakers, but at 0.2 miles from the bridge, a second blackout occurred. The emergency generator maintained power to emergency systems, and generator 2 automatically started, restoring power to the HV bus. The senior pilot ordered the rudder hard to port at 0127:23, but the lack of propulsion hampered steering efforts. Despite the crew regaining electrical power before the ship struck the bridge, they were unable to restore propulsion.


*This summary was created using ChatGPT-4o

  • @aodhsishaj
    link
    216 months ago

    I’m curious as to what cost saving measures led to the electrical problems.

    • @Everythingispenguins
      link
      36 months ago

      The cost saving measures that caused this was not having tug escorts to the far side to the bridge. Two appropriately sized tugs could have stopped or turned the boat without a problem.

  • @ProfessorScience
    link
    English
    146 months ago

    The emergency generator was not configured to power the ship, the report said.

    So was it just there for decoration or…

    • @shaun
      link
      23
      edit-2
      6 months ago

      The emergency generator for all vessels is typically tiny compared to the standard generators (of which you have multiple, maybe 4 on this ship).

      It’s basically just there to keep the emergency lights on and any other equipment you need to work to get everything else back up and running.

      • @ProfessorScience
        link
        English
        86 months ago

        S’pose that’s fair. It does seem odd that the report would say the generator was “not configured” to power the ship, rather than not capable of it.

        • @[email protected]
          link
          fedilink
          16 months ago

          Both of those can be true, no? It was not capable to power the ship because it was not configured to do so.

          • @ProfessorScience
            link
            English
            26 months ago

            Maybe. But can it be configured to power the ship? If so why wasn’t it?

    • @Treczoks
      link
      86 months ago

      The emergency generator is just there to power absolute emergency equipment: some lights, radio, onboard communication, stuff like that. Not for powering the whole ship. For that there are the main generators, of which that ship has four, and you need several of them running to actually do something.

      The emergency generator is something the size of a trucks’ engine. The main generators are more like the size of trucks.