    Customer reporting pool pump not working. Only getting 1.6V at the receptacle, all others showing 120V. One wire in it, so obviously last one on the circuit. Went to the one before it, found this. All of them backstabbed. Reterminated them all before I left

    • m-p{3}
      link
      fedilink
      21 year ago

      I’m not an electrician, but I always found the backstab a terrible idea, compared to the screw connectors…

      • @[email protected]OP
        link
        fedilink
        31 year ago

        On receptacles it generally is a bad idea. Things being plugged & unplugged all the time makes for little micro movements of the device that will wear at the thin connection and over time cause a problem. It’s not as big of a problem for switches, not as much movement and beating around

  • @Meltbox
    link
    61 year ago

    It’s nutty to me to even manufacture these with backstab holes.

    I get it’s technically allowed.

    Coming from some background in HV battery work, the whole way we wire residential sketches me out to no end to be honest.

  • @Fosheze
    link
    English
    61 year ago

    Refrigeration tech here, why is using the back stab holes a bad thing?

    • @[email protected]
      link
      fedilink
      English
      71 year ago

      Backstab holes create a pretty poor connection with very little surface area and light pressure compared to the screw terminals. It may make a half-decent connection at first, but over time as the contacts oxidize/corrode they become a high resistance point and heat up a lot. Terrible design.

    • @[email protected]M
      link
      fedilink
      21 year ago

      They always fail spectacularly. I’ve seen countless melted receptacles, usually due to a backstab connection and a high power load plugged in downstream. Since I’m in Canada, space heaters are one of the worst culprits.

  • @[email protected]
    link
    fedilink
    21 year ago

    backstab is terrible, but its there and people use it. I always purchase commercial spec grade, they have no backstabs so after i leave i feel confident no ass will add a cct to the backstabs. If we want to rid the world of it we need to start a petition

  • @[email protected]
    link
    fedilink
    11 year ago

    The only time I used backstab was when working for a boss who timed me.

    “If you’re taking longer than a minute a plug, you’re not going to last!”