I have a centrally located dual flue chimney that serves both two wood stoves and an oil furnace. In the basement there are galvanized steel clean out doors for each flue. When I run the kitchen exhaust, a bathroom exhaust, the dryer, or the central vacuum the basement starts to smell like creosote right around the clean out doors.

I assume the issue is the house is too air tight and the chimney clean outs happen to be the easiest draft entry. Question is, what do I do about it? Should I seal up the clean out doors tighter before I use the wood stoves this winter?

  • @[email protected]
    link
    fedilink
    71 year ago

    Some building codes require "make up air supply " for kitchen exhaust fans. It’s an vent that opens automatically to let air into the house when the exhaust fan is turned on

    • @RabbitFighterOP
      link
      41 year ago

      That sounds like the search term I needed. Now to do some research.